Home > Services > Energy > Briefing II

Energy Audit

Case Study II


Date: February 2005

Location: Central, Hong Kong

Type: Composite Commercial Building

This sanitised energy audit briefing is one element of a comprehensive energy audit report

An energy audit uncovered several opportunities to conserve waste energy, lower operating expenses and save money. One particular discovery, is an interesting an example because Kelcroft philosophy, namely details matter.

It also demonstrates that a relatively small modification can create substantial savings over time.

The Kelcroft energy audit uncovered an alarming fact, the entire building’s central chilled water plant was regularly started every Sunday to serve a single room.


Synopsis

The building was fitted with a standard plant arrangement,  a central chilled water air conditioning system, comprising:

  • air-cooled liquid chillers
  • chilled water pumps (2 duty/1 standby)
  • pressure compensated bypass valve
  • common riser serving fan coil units
  • control on/off 2-port control valve


Building Characteristics

Building operation were outsourced to a building management company, plant stop/start operations was conducted manually.

One tenant required air-conditioning for a single room (approx. 500 sq. ft.).

Therefore the building management company started the chilled water plant, including pumps and ancillaries, and operated same for four hours, every Sunday to provide comfort cooling.

The system turndown ratio was unable to cope with the "load" creating gross energy inefficiency. The control system was hunting, and causing operational instabilities.

Numerical Analysis

Energy auditing is economics driven; the goal to identify feasible energy and cost savings.

Calculations indicated that corrective action would save more than HK$40,000 per annum, with a payback period of less than one year. In addition, a corrective action would save more than 2,400 Kg carbon dioxide emitted every year.

Other savings accrue, extended life of the equipment and reduced maintenance costs.

Conclusions

The air-conditioning system had been operated inefficiently, causing stability (hunting) problems, and calculations validated the significant waste of energy.

Since operating requirements, characteristics are not static, and vary throughout the lifespan of a building, is a timely reminder to conduct an annual energy audit.

This briefing is one element of a comprehensive energy audit report


Energy Audit

For professional, independent energy audit, energy surveys and energy engineering advice call Kelcroft today. For further information regarding energy efficiency and energy conservation call Mr John Herbert telephone (852) 2335 9830, facsimile (852) 2335 9862 or email us

TOP